Logo Image Logo Image
Produktfoto
Technical data
  • Power distribution cables
    acc. to DIN VDE 0276-603 /
    HD 603 S1 / IEC 60502
  • Temperature range
    flexing  -5°C  to  +50°C
    fixed installation  -40°C  to  +70°C
  • Permissible conductor operating
    temperature 
    +70°C
  • Permissible short circuit temperature
    (short circuit duration max. 5 s)
    ≤ 300 mm² +160°C
    > 300 mm² +140°C
  • Nominal voltage
    U0/U 0,6/1 kV
  • Test voltage
    4 kV
  • Minimum bending radius
    single core 15x outer Ø
    multi core 12x outer Ø
  • Caloric load values
    see "Technical Information"
Cable structure
  • Aluminium conductor,  
    single wire or multi wire acc. to
    DIN VDE 0295 cl.1 or cl.2 /
    IEC 60228 cl.1 or cl.2
  • Core insulation of PVC
    compound type DIV4
    acc. to HD 603 S1
  • Core identification acc. to
    DIN VDE 0293-308 / 0276-603
  • Cores concentrically stranded
  • Common core sheath
  • Outer sheath of PVC
    compound type DMV5
    acc. to HD 603 S1
  • Sheath colour: black
Properties
  • The materials used during manufacturing
    are cadmium-free, contain no silicone
    and are free from substances harmful
    to the wetting properties of lacquers
     
Tests
  • Flame retardant acc. to
    DIN VDE 0482-332-1-2 /
    DIN EN 60332-1-2 / IEC 60332-1-2
Highest permissible voltage
  • Direct current systems
    - Conductor/conductor 1,8 kV
    - Conductor/earth  0,9 kV
  • Alternating current systems
    - Single phase systems
       both outer conductors insulated 1,4 kV
    - Single phase systems
       one outer conductor earthed 0,7 kV
  • Three phase systems 1,2 kV
Note
  • re = round conductor, single wire
    rm = round conductor, multi wire
    se = sectional conductor, single wire
    sm = sectional conductor, mutli wire
  • J-version = with GN-YE conductor
    O-version = without GN-YE conductor
  • Part no. 32182, 32183, 32199,  
    32258, 34047 in reference to VDE
    Designation (N)AYY
  • The conductor is metrically constructed
    (mm²). The AWG designation is
    approximate and purely informative.
Application
Power cables for energy supply are installed in open air, in underground, in water, in concrete, indoors, in cable ducts, power stations, for industry and distribution boards as well as in subscriber networks, where mechanical damages are not be expected.
CE = Product conforms with Low-Voltage Directive 2014/35/EU.
Downloads
Data sheet

No.cores x
cross-sec.
mm²

Outer Ø

app. mm

Alu weight

kg / km

Weight

app. kg / km

J type

Part no.

AWG-No.

O type

Part no.

AWG-No.

4 x 16

re

20,0

186,0

750,0

32301

6

-

32184

6

-
4 x 25

re

26,0

290,0

950,0

32302

4

-

32185

4

-
4 x 35

re

28,5

406,0

1120,0

32303

2

-

32186

2

-
4 x 50

se

30,0

580,0

1151,0

32304

1

-

32187

1

-
4 x 70

se

35,0

812,0

1549,0

32305

2/0

-

32188

2/0

-
4 x 95

se

39,5

1102,0

2030,0

32306

3/0

-

32189

3/0

-
4 x 95

sm

39,5

1102,0

2030,0

32177

3/0

-

32190

3/0

-
4 x 120

se

44,0

1392,0

2400,0

32307

4/0

-

32191

4/0

-
4 x 120

sm

44,0

1392,0

2400,0

32178

4/0

-

32192

4/0

-
4 x 150

se

46,0

1740,0

3030,0

32308

300 kcmil

-

32193

300 kcmil

-
4 x 150

sm

46,0

1740,0

3030,0

32179

300 kcmil

-

32194

300 kcmil

-
4 x 185

se

51,0

2146,0

3650,0

32309

350 kcmil

-

32195

350 kcmil

-
4 x 185

sm

51,0

2146,0

3650,0

32180

350 kcmil

-

32196

350 kcmil

-
4 x 240

se

56,0

2784,0

4800,0

32310

500 kcmil

-

32197

500 kcmil

-
4 x 240

sm

56,0

2784,0

4800,0

32181

500 kcmil

-

32198

500 kcmil

-
4 x 300

se

56,0

3480,0

5596,0

32182

600 kcmil

-

32199

600 kcmil

-
4 x 300

sm

64,0

3480,0

5596,0

32183

600 kcmil

-

32258