NA2XY

Power cable, 0,6/1 kV, higher current carrying capacity

Logo Image Logo Image
Produktfoto
Technical data
  • Power distribution cables
    acc. to DIN VDE 0276-603 /
    HD 603 S1 / IEC 60502
  • Temperature range
    flexing  -5°C  to  +50°C
    fixed installation  -40°C  to  +70°C
  • Permissible conductor operating
    temperature
      +90°C
  • Permissible short circuit temperature
    (short circuit duration max. 5 s)
    +250°C
  • Nominal voltage
    U0/U 0,6/1 kV
  • Test voltage
    4 kV
  • Minimum bending radius
    single core 15x outer Ø
    multi core 12x outer Ø
Cable structure
  • Aluminium conductor,  
    single wire or multi wire acc. to
    DIN VDE 0295 cl.1 or cl.2 /
    IEC 60228 cl.1 or cl.2
  • Core insulation of cross-linked
    polyethylene (XLPE)
    compound type DIX3
    acc. to HD 603 S1
  • Core identification acc. to
    DIN VDE 0293-308 / 0276-603
  • Cores concentrically stranded
  • Outer sheath of PVC
    compound type DMV6
    acc. to HD 603 S1
  • Sheath colour: black
Properties
  • The materials used during manufacturing
    are cadmium-free, contain no silicone
    and are free from substances harmful
    to the wetting properties of lacquers
Tests
  • Flame retardant acc. to
    DIN VDE 0482-332-1-2 /
    DIN EN 60332-1-2 / IEC 60332-1-2
Highest permissible voltage
  • Direct current systems
    - Conductor/conductor 1,8 kV
    - Conductor/earth  0,9 kV
  • Alternating current systems
    - Single phase systems
       both outer conductors insulated 1,4 kV
    - Single phase systems
       one outer conductor earthed 0,7 kV
  • Three phase systems 1,2 kV
Note
  • re = round conductor, single wire
    rm = round conductor, multi wire
    se = sectional conductor, single wire
  • J-version = with GN-YE conductor
    O-version = without GN-YE conductor
  • The conductor is metrically constructed
    (mm²). The AWG designation is
    approximate and purely informative.
Application
Power distribution cables for use in underground, in water, outdoors, in concrete, indoors, in cable ducts, for power stations, industrial applications and switching systems, as well as in local networks if no mechanical damage is expected. Respecting the permissible operating temperature at the conductor of +90°C permits a higher current carrying capacity than PVC insulated power distribution cables.
CE = Product conforms with Low-Voltage Directive 2014/35/EU.
Downloads
Data sheet
Certificate of compliance

No.cores x
cross-sec.
mm²

Outer Ø

app. mm

Alu weight

kg / km

Weight

app. kg / km

J type

Part no.

AWG-No.

O type

Part no.

AWG-No.

1 x 16

re

11,5

47,0

98,0

33113

6

-

33125

6

-
1 x 25

re

12,5

73,0

150,0

33114

4

-

33126

4

-
1 x 35

re

13,5

102,0

241,0

33115

2

-

33127

2

-
1 x 50

rm

15,5

145,0

357,0

33116

1

-

33128

1

-
1 x 70

rm

17,0

203,0

409,0

33117

2/0

-

33129

2/0

-
1 x 95

rm

19,0

276,0

570,0

33118

3/0

-

33130

3/0

-
1 x 120

rm

20,5

348,0

590,0

33119

4/0

-

33131

4/0

-
1 x 150

rm

23,0

435,0

804,0

33120

300 kcmil

-

33132

300 kcmil

-
1 x 185

rm

25,5

537,0

978,0

33121

350 kcmil

-

33133

350 kcmil

-
1 x 240

rm

28,5

696,0

1253,0

33122

500 kcmil

-

33134

500 kcmil

-
1 x 300

rm

30,0

870,0

1394,0

33123

600 kcmil

-

33135

600 kcmil

-
1 x 400

rm

34,0

1160,0

1890,0

33124

750 kcmil

-

33136

750 kcmil

-
4 x 16

re

21,5

186,0

750,0

33137

6

-

33147

6

-
4 x 25

re

27,5

290,0

950,0

33138

4

-

33148

4

-
4 x 35

re

27,5

406,0

1120,0

33139

2

-

33149

2

-
4 x 50

se

28,0

580,0

1251,0

33140

1

-

33150

1

-
4 x 70

se

34,0

812,0

1548,0

33141

2/0

-

33151

2/0

-
4 x 95

se

36,5

1102,0

2030,0

33142

3/0

-

33152

3/0

-
4 x 120

se

39,5

1392,0

2400,0

33143

4/0

-

33153

4/0

-
4 x 150

se

43,5

1740,0

3030,0

33144

300 kcmil

-

33154

300 kcmil

-
4 x 185

se

48,0

2146,0

3650,0

33145

350 kcmil

-

33155

350 kcmil

-
4 x 240

se

53,0

2784,0

4800,0

33146

500 kcmil

-

33156

500 kcmil

-