TRONIC (LiYY)

flexible, colour coded to DIN 47100, meter marking

Logo Image
Produktfoto
Technical data
  • Special-PVC data cables adapted
    to DIN VDE 0812
  • Temperature range
    flexing -5°C  to  +80°C
    fixed installation -40°C  to  +80°C
  • Operating peak voltage
    (not for heavy current installation purposes)
    0,14 mm²  350 V
    ≥  0,25 mm²  500 V
  • Test voltage
    up to 0,25 mm²  1200 V
    from 0,34 mm²  2000 V
  • Breakdown voltage
    up to 0,25 mm²  2400 V
    from 0,34 mm²  4000 V
  • Mutual capacitance  at 800 Hz
    0,14 mm²  approx. 120 pF/m
    0,25 mm²  approx. 150 pF/m
  • Inductance
    approx. 0,65 mH/km
  • Impedance
    approx. 78 Ohm
  • Minimum bending radius
    flexing 7,5x outer Ø
    fixed installation 4x outer Ø
Cable structure
  • Bare copper conductor,
    from 0,5 mm²  fine wire acc. to
    DIN VDE 0295 cl.5 / IEC 60228 cl.5
  • Conductor construction:
    0,14 mm²  approx. 18x0,1 mm
    0,25 mm²  approx. 14x0,15 mm
    0,34 mm²  = 7x0,25 mm
  • Core insulation of special PVC
    compound type TI2 to
    DIN VDE 0207-363-3 / DIN EN 50363-3
  • Core identification adapted to
    DIN 47100, without colour repetition
  • Cores stranded in layers with
    optimal lay length
  • Outer sheath of special PVC
    compound type TM2 to
    DIN VDE 0207-363-4-1/DIN EN 50363-4-1
  • Sheath colour: grey (RAL 7001)
  • With meter marking
Properties
  • Extensively oil resistant,
    oil-/chemical resistance
    see "Technical Information"
  • The materials used during manufacturing
    are cadmium-free, contain no silicone
    and are free from substances harmful
    to the wetting properties of lacquers
Tests
  • PVC self-extinguishing and flame retardant
    acc. to DIN VDE 0482-332-1-2 /
    DIN EN 60332-1-2 / IEC 60332-1-2
Note
  • Also available in paired version, see
    HELUKABEL®-PAAR-TRONIC
  • The conductor is metrically constructed
    (mm²).  The AWG designation is
    approximate and purely informative.
  • Screened analogue type:
    TRONIC-CY (LiY-CY)
Application
These cables are used for flexible use with free movement without tensile stress or forced movements in dry, moist and wet rooms but not suitable for open air, wherever the construction requirements call for a minimum outer diameter, TRONIC is the suitable cable to use. This applies especially to such areas as tool making and machine industries as well as electronic, computer, measurement and control sectors.
CE = Product conforms with Low-Voltage Directive 2014/35/EU.
Downloads
Data sheet
Certificate of compliance

Part no.

No.cores x
cross-sec.
mm²

Outer Ø

app. mm

Cop.
weight

kg / km

Weight

app. kg / km

AWG-No.

18001

2 x 0,14

3,5

2,7

13,0

26

18002

3 x 0,14

3,7

4,0

16,0

26

18003

4 x 0,14

3,9

5,4

19,0

26

18004

5 x 0,14

4,3

6,7

22,0

26

18005

6 x 0,14

4,6

8,1

25,0

26

18006

7 x 0,14

4,6

9,4

28,0

26

18007

8 x 0,14

5,5

10,7

35,0

26

18008

10 x 0,14

5,9

13,4

41,0

26

18009

12 x 0,14

6,1

16,1

48,0

26

18010

14 x 0,14

6,3

18,8

53,0

26