NYCY

Power cable, 0,6/1 kV, with concentric copper conductor

Logo Image Logo Image
Produktfoto
Technical data
  • Power and control cable
    acc. to DIN VDE 0276-603 /
    HD 603 S1 / IEC 60502
    7 cores and above
    acc. to DIN VDE 0276-627 /
    HD 627 S1 / IEC 60502
  • Temperature range
    flexing  -5°C  to  +50°C
    fixed installation  -40°C  to  +70°C
  • Permissible operating temperature
    at conductor  +70°C
  • Permissible short circuit temperature
    (short circuit duration max. 5 s)
    +160°C
  • Nominal voltage
    U0/U 0,6/1 kV
  • Test voltage
    4 kV
  • Minimum bending radius
    single core 15x outer Ø
    multi core 12x outer Ø
  • Caloric load values
    see "Technical Information"
Cable structure
  • Bare copper conductor,
    single wire acc. to
    DIN VDE 0295 cl.1 / IEC 60228 cl.1
  • Core insulation of PVC
    compound type DIV4
    acc. to HD 603 S1
  • Core identification
    acc.to DIN VDE 0293-308
  • Cores stranded in concentric layers
  • Filling compound
  • Concentric conductor in inner layer of
    round copper wires, outer layer with
    copper tape
  • Outer sheath of PVC
    compound type DMV5
    acc. to HD 603 S1
  • Sheath colour: black
Properties
  • The materials used during manufacturing
    are cadmium-free, contain no silicone
    and are free from substances harmful
    to the wetting properties of lacquers
Tests
  • Flame retardant acc. to
    DIN VDE 0482-332-1-2 /
    DIN EN 60332-1-2 / IEC 60332-1-2
Highest permissible voltage
  • Direct current systems
    - Conductor/conductor 1,8 kV
    - Conductor/earth  0,9 kV
  • Alternating current systems
    - Single phase systems
      both outer conductors insulated 1,4 kV
    - Single phase systems
      one outer conductor earthed 0,7 kV
  • Three phase systems 1,2 kV with
    concentric conductor and a cross
    section of 240 mm² and above 3,6 kV
Note
  • re = round conductor, single wire
  • The conductor is metrically constructed
    (mm²). The AWG designation is
    approximate and purely informative.
Application
Power cables for energy supply are used for industry and distribution boards, power stations, house connecting boxes and street lighting as well as control cable for the transmission of control impulses and test datas. Overall, where increased electrical and also mechanical protection are required. Those cables are installed in open air, in underground, in water, in concrete, indoors and in cable ducts. The concentric conductor (C) may be used as PE, PEN conductor or as a shield according to national regulations.
CE = Product conforms with Low-Voltage Directive 2014/35/EU.
Downloads
Data sheet
Certificate of compliance

Part no.

No.cores x
cross-sec.
mm²

Outer Ø

app. mm

Cop.
weight

kg / km

Weight

app. kg / km

AWG-No.

32200

1 x 10

re / 10

11,0

216,0

280,0

8

32201

1 x 16

re / 16

12,0

336,0

440,0

6

32202

2 x 1,5

re / 1,5

13,0

52,0

205,0

16

32203

2 x 2,5

re / 2,5

13,5

80,0

270,0

14

32204

2 x 4

re / 4

15,5

123,0

360,0

12

32205

2 x 6

re / 6

17,0

182,0

435,0

10

32206

2 x 10

re / 10

19,5

312,0

590,0

8

32207

2 x 16

re / 16

20,5

489,0

820,0

6

32208

3 x 1,5

re / 1,5

13,5

66,0

225,0

16

32209

3 x 2,5

re / 2,5

14,5

104,0

290,0

14

32210

3 x 4

re / 4

16,5

161,0

400,0