N2XH

Power cable, 0.6/1 kV, halogen-free, without functionality

Logo Image Logo Image
Produktfoto
Technical data
  • Power and control cable
    acc. to DIN VDE 0276-604 /
    HD 604 S1-1+5G
  • Temperature range
    during installation -5°C  to  +50°C
    fixed installation -30°C  to  +90°C
  • Permissible conductor operating
    temperature
      +90°C
  • Nominal voltage
    U0/U 0,6/1 kV
  • Test voltage
    4 kV
  • Minimum bending radius
    single-core 15x cable Ø
    multi-core 12x cable Ø
  • Caloric load values
    see "Technical Information"
Cable structure
  • Bare copper conductor,
    single wire or multi wire acc. to
    DIN VDE 0295 cl.1 or cl.2 /
    IEC 60228 cl.1 or cl.2
  • Core insulation of cross-linked
    polyethylene (XLPE)
    compound type 2XI1
    acc. to HD 604 S1
  • Core identification
    acc. to DIN VDE 0293-308
  • Core identification for 3+½ conductor
    J-type: GN-YE (½), BN, BK, GY
    O-type: BU (½), BN, BK, GY
  • Cores stranded in layers
    (for multi-core cables)
  • Overall filled inner sheath
  • Covered by filling compound or taping
  • Outer sheath of thermoplastic
    polyolefin, compound type HM4
    acc. to HD 604 S1
  • Sheath colour: black
Properties
  • Halogen free, no separation
    of corrosive and toxic gases
  • Limited propagation of fire
  • Low smoke development
  • The materials used during manufacturing
    are cadmium-free, contain no silicone
    and are free from substances harmful
    to the wetting properties of lacquers
Tests
  • Flame test acc. to
    DIN VDE 0482-332-3-24
    DIN EN 60332-3-24 / IEC 60332-3-24
  • Corrosiveness of combustion gases
    acc. to DIN VDE 0482-267 /
    DIN EN 50267-2-2 / IEC 60754-2
  • Halogen-free acc. to
    DIN VDE 0482-267 /
    DIN EN 50267-2-1 / IEC 60754-1
  • Smoke density acc. to
    DIN VDE 0482-1034-1+2 /
    DIN EN 61034-1+2 / IEC 61034-1+2
Note
  • re = round conductor, single-wire
    rm = round conductor, multi-wire
    sm = sectional conductor, mutli-wire
  • J-version = with GN-YE conductor
    O-version = without GN-YE conductor
  • The conductor is metrically constructed
    (mm²).  The AWG designation is
    approximate and purely informative.
  • LS0H = Low Smoke Zero Halogen
Application
Halogen-free power cables with enhanced characteristics in case of fire are used for applications where harm to human life and damage to property must be prevented in the event of fire, e. g. in power stations, industrial installations, communal establishments, hotels, airports, underground stations, railway stations, hospitals department stores, banks, schools theaters, multi-storey buildings, process control centres etc. Suitable for fixed installation in dry, damp or wet environments, in, above, on and beneath plaster as well as in masonary walls and in concrete. These cables are suitable for outdoor applications and in underground by using in conduits or tubes. For the installation in conduit all precautions must be taken that no accumulation of water can occur in the pipes.
CE = Product conforms with Low-Voltage Directive 2014/35/EU.
Downloads
Data sheet
Certificate of compliance

Part no.

No.cores x
cross-sec.
mm²

Outer Ø

app. mm

Cop.
weight

kg / km

Weight

app. kg / km

AWG-No.

J type

O type

 

53558

1 x 1,5   rm

6,0

14,4

41,0

16

 

53559

1 x 2,5   rm

6,5

24,0

53,0

14

53100

53248

1 x 4   re

8,0

39,0

68,0

12

53101

53249

1 x 6   re

9,0

58,0

90,0

10

53102

53250

1 x 10   re

9,0

96,0

140,0

8

53103

53251

1 x 16   re

10,0

154,0

190,0

6

53104

53252

1 x 25   rm

11,0

240,0