HELUTHERM® 145 MULTI-C

flexible, cross-linked, halogen-free, screened, EMC-preferred type

Logo Image Logo Image
Produktfoto
Technical data
  • Temperature-resistant and halogen-free
    connection and control cable
  • Temperature range
    flexing -35°C to +120°C
    fixed installation -55°C to +145°C
    in short-circuit +250°C
  • Nominal voltage
    up to 1,0 mm² U0/U 300/500 V
    from 1,5 mm² U0/U 450/750 V
    with protected fixed installation
    from 1,5 mm² U0/U 600/1000 V
  • Test voltage
    3000 V
  • Minimum bending radius
    in operation 8x cable Ø
    fixed installation 4x cable Ø
  • Coupling resistance
    max. 250 Ohm/km
  • Caloric load values
    see "Technical Informations"
  • Power ratings table
    see "Technical Informations"
  • Approval
    Germanischer Lloyd
Cable structure
  • Tinned copper conductor, to
    DIN VDE 0295 cl.5, fine wire,
    BS 6360 cl.5, IEC 60228 cl.5
  • Core insulation of cross-linked,
    halogen-free polyolefin-copolymer
  • Core identification black cores with
    continuous white numbering
  • Cores stranded in layers with
    optimal lay length
  • Tinned copper braided screen,
    approx. 85% coverage
  • Outer sheath of cross-linked,
    halogen-free polyolefin-copolymer
  • Sheath colour: black
  • With meter marking
Properties
  • Lower propagation of fire
  • Low development of smoke and fumes
  • Good abrasion and notch resistance
  • Good resistance to oils and weathering
  • Resistant to UV radiation and ozone
  • Resistant to soldering temperatures
  • Thermal class B
  • These control cables are resistant to
    melting, even when in contact with a
    soldering iron at temperatures of between
    300°C and 380°C, because of the
    cross-linking for the insulation material
  • The materials used during manufacturing
    are cadmium-free, contain no silicone
    and are free from substances harmful
    to the wetting properties of lacquers
Tests
  • Flame test (unit flame test) acc. to
    DIN VDE 0482-332-3-22, BS 4066 Teil 3,
    DIN EN 60332-3-22, IEC 60332-3-22
    (previously DIN VDE 0472
    part 804 test method C)
  • Flame test (cable) acc. to
    DIN VDE 0482-332-1-2, DIN EN 60332-1-2,
    IEC 60332-1-2 (equivalent DIN VDE 0472
    part 804 test method B)
  • Corrosiveness of combustion gases
    acc. to DIN VDE 0482 part 267,
    DIN EN 50267-2-2, IEC 60754-2
    (equivalent DIN VDE 0472 part 813)
  • Halogen-free
    acc. to DIN VDE 0482 part 267,
    DIN EN 50267-2-1, IEC 60754-1
    (equivalent DIN VDE 0472 part 815)
  • Smoke density
    acc. to DIN VDE 0482 part 1034-1+2,
    DIN EN 61034-1+2, IEC 61034-1+2,
    BS 7622 part 1+2
    (previously DIN VDE 0472 part 816)
Note
  • Also available in other colours on request
  • AWG sizes are approximate equivalent
    values. The actual cross section is in mm².
  • Unscreened analogue type:
    HELUTHERM® 145 MULTI
Application
These halogen-free, cross-linked and temperature resistant wiring and control cables with enhanced fire-behaviour properties are used for wiring up the lighting fixtures, heaters, electric machines (temperature class B), switching systems and distribution switchboards. A very long service life is also given on account of their excellent high-temperature stability. These cables exhibit good resistance to weathering as well as being very stable to