OZ-BL

outer sheath blue, intrinsic safety, flexible, meter marking

Logo Image Logo Image
Produktfoto
Technical data
  • Control cable, special PVC with blue outer
    sheath for hazardous areas to
    hazard type -i- (= intrinsically safe)
  • For intrinsically safe installation acc. to
    DIN EN 60079-14 and IEC 60079-14
    section 12.2.2 (VDE 0165 part 1)
  • Temperature range
    flexing -15°C to +80°C
    fixed installation -40°C to +80°C
  • Nominal voltage
    U0/U 300/500 V
  • Test voltage
    3000 V
  • Breakdown voltage
    min. 6000 V
  • Mutual capacitance
    core/core  approx. 120 nF/km
  • Inductance
    approx. 0,68 mH/km
  • Minimum bending radius
    flexing 7,5x cable Ø
    fixed installation 4x cable Ø
  • Radiation resistance
    up to 80x106 cJ/kg (up to 80 Mrad)
Cable structure
  • Bare copper conductor, to
    DIN VDE 0295 cl.5, fine wire,
    BS 6360 cl.5, IEC 60228 cl.5
  • Core insulation of special PVC
    compound type Z 7225
  • Core identification to DIN VDE 0293
    black cores with continuous white
    numbering
  • without GN-YE conductor
  • Cores stranded in layers with
    optimal lay length
  • Outer sheath of special PVC
    compound type TM2 to
    DIN VDE 0207-363-4-1/DIN EN 50363-4-1
  • Sheath colour: blue (RAL 5015)
  • With meter marking
Properties
  • Extensively oil resistant,
    oil-/chemical resistance
    see table Technical Informations
  • The materials used during manufacturing
    are cadmium-free, contain no silicone
    and are free from substances harmful
    to the wetting properties of lacquers
Tests
  • PVC self-extinguishing and flame retardant
    acc. to DIN VDE 0482-332-1-2,
    DIN EN 60332-1-2/IEC 60332-1 (equivalent
    DIN VDE 0472 part 804 test method B)
Note
  • For underground laying use NYY with blue
    outer sheath.
  • AWG sizes are approximate equivalent
    values. The actual cross section is in mm².
  • Instrumentation cable RE-2Y(St)Yv with blue
    outer sheath see Data and Computer Cables
Application
For hazardous areas the cables with special marking (blue) (hazard type-i-) used as flexible control and measuring cables to meet the requirements for the installation of electrical apparatus. These installations are not earthed and require a separate power circuit. Those cables are not suitable for underground laying.
CE = Product conforms with Low-Voltage Directive 2014/35/EU.
Downloads
Data sheet
Certificate of compliance

Part no.

No.cores x
cross-sec.
mm²

Outer Ø

approx. mm

Cop.
weight

kg / km

Weight

approx. kg / km

AWG-No.

14001

2 x 0,75

5,3

14,4

46,0