RE-2Y(St)Yv PiMF

Instrumentation calbe, pairs screened, reinforced outer sheath, meter marking

Logo Image
Produktfoto
Technical data
  • Special core insulation of PE
  • Conductor resistance
    0,5 mm² = max. 39,2 Ohm/km
    1,3 mm² = max. 14,2 Ohm/km
  • Temperature range
    flexing -5°C to +50°C
    fixed installation -40°C to +70°C
  • Operating peak voltage max. 300 V
    (not for heavy current installation purposes)
  • Test voltage
    core/core 2000 V
    core/screen 1000 V
  • Insulation resistance
    min. 5 GOhm x km
  • Mutual capacitance (approx. value)
    at 800 Hz
    core/core 0,5 mm² = 75 nF/km
    core/core 1,3 mm² = 100 nF/km
  • Inductance max. 0,75 mH/km
  • Cross-talk attenuation
    min. 1,02 dB/km at 60 kHz
  • Minimum bending radius
    7,5x cable Ø
Cable structure
  • Bare copper stranded wires
    0,5 mm 2 =7x0,3 mm
    1,3 mm² = 7x0,49 mm
  • Core insulation of PE
  • Cores coloured
    with number print 1/1, 2/2 etc.
    a-core = BK; b-core = WH
  • Cores twisted in pairs with optimum pitch
  • PiMF (pair in metal foil),
    PiMF structure: foil taping,
    Cu-tinned drain-wire 0,6 mm Ø,
    plastic coated alu-foil
    and foil wrapping
  • PiMFe stranded in layer,
    1 communication core 0,5 mm²,
    PE-insulated orange (communication core
    for multicore version)
  • Electrostatic screen (St) of plastics-coated
    metal foil and tinned drain-wire 0,5 mm²
    (7x0,3 mm)
  • Outer sheath of PVC, reinforced,
    black (RAL 9005) or blue (RAL 5015)
  • With meter marking
  • Wall-thickness to DIN VDE 0816 part 1,
    table 7, col. 1
Properties
  • The materials used during manufacturing
    are cadmium-free, contain no silicone
    and are free from substances harmful
    to the wetting properties of lacquers
Tests
  • self-extinguishing and flame retardant
    acc. to DIN VDE 0482-332-1-2,
    DIN EN 60332-1-2/IEC 60332-1 (equivalent
    DIN VDE 0472 part 804 test method B)
Note
  • Cop.weight including communication core
    and drain-wire.
  • Control cable with blue outer sheath, see
    Flexible Control Cables
  • with blue outer sheath for hazardous areas
    to hazard type -i- for intrinsically safe
    installation acc. to DIN EN 60079-14
    section 12.2.2 (VDE 0165 part 1)
  • AWG sizes are approximate equivalent
    values. The actual cross section is in mm².
Application
Instrumentation cables are used in data processing and process control. The individual screening of the pairs guarantee high cross-talk attenuation. The electrostatic screen protect the screened pairs against outer electrostatic interference fields. Low level of line attenuations and low mutual capacitances enable long transmission distances and fast pulse acceleration. Instrumentation cables are suitable for fixed installations in damp locations, in open spaces and for underground laying.
CE = Product conforms with Low-Voltage Directive 2014/35/EU.
Downloads
Data sheet
Certificate of compliance

Part no.

No.pairs x
cross-sec.
mm²

Sheath
colour

Outer Ø

approx. mm

Cop.
weight

kg / km

Weight

approx. kg / km

AWG-No.

20115

2 x 2 x 0,5

black

11,0

35,0

128,0

20

20116

4 x 2 x 0,5

black

12,6

60,0

170,0

20

21535

6 x 2 x 0,5

black

14,6

82,0

215,0

20

20117

8 x 2 x 0,5

black

15,5

121,0

246,0