RE-2Y(St)Yv

instrumentation cable, reinforced outer sheath, meter marking

Logo Image
Produktfoto
Technical data
  • Special core insulation of PE
  • Conductor resistance
    0,5 mm²: max. 39,2 Ohm/km
    0,75 mm²: max. 24,6 Ohm/km
    1,3 mm²: max. 14,2 Ohm/km
  • Temperature range
    flexing -5°C to +50°C
    fixed installation -40°C to +70°C
  • Operating peak voltage max. 300 V
    (not for heavy current installation purposes)
  • Test voltage
    core/core 2000 V
    core/screen 1000 V
  • Insulation resistance
    min. 5 GOhm x km
  • Mutual capacitance at 800 Hz
    core/core 0,5 mm²: 60 nF/km
    for 1 and 2 pairs: 75 nF/km
    core/core 0,75 mm²: 65 nF/km
    for 1 and 2 pairs: 110 nF/km
    core/core 1,3 mm²: 75 nF/km
    for 1 and 2 pairs: 100 nF/km
  • Inductance max. 0,75 mH/km
  • Cross-talk attenuation
    min. 0,88 dB/km at 60 kHz
  • Minimum bending radius
    7,5x cable Ø
Cable structure
  • Bare copper conductor, multi-wires
  • Conductor construction:
    0,5 mm² = 7x0,3 mm
    0,75 mm² = 7x0,37 mm
    1,3 mm² = 7x0,49 mm
  • Core insulation of PE
  • Cores coloured
    with number print 1/1, 2/2 etc.
    pair: a-core = BK; b-core = WH
    triple: a-core = BK; b-core = WH;
    c-core = RD
  • Cores twisted to pairs with optimum pitch
  • Pairs stranded in layer
  • 1 communication core 0,5 mm², PE-insulated,
    orange (for multicore version)
  • Foil wrapping
  • Electrostatic screen (St) of plastics-coated
    metal foil
  • Tinned drain-wire, 0,5 mm² = 7x0,3 mm
  • Outer sheath of PVC, reinforced,
    black (RAL 9005) or blue (RAL 5015)
  • With meter marking
  • Wall-thickness to DIN VDE 0816 part 1,
    table 7, col. 1
Properties
  • The electrostatic screen protect the
    screened pairs against outer electrostatic
    interference fields
  • Low level of line attenuations and low
    mutual capacitances enable long
    transmission distances and fast pulse
    acceleration
  • The materials used during manufacturing
    are cadmium-free, contain no silicone
    and are free from substances harmful
    to the wetting properties of lacquers
Tests
  • self-extinguishing and flame retardant
    acc. to DIN VDE 0482-332-1-2,
    DIN EN 60332-1-2, IEC 60332-1 (equivalent
    DIN VDE 0472 part 804 test method B)
Note
  • Cop.Weight including communication core
    and drain-wire.
  • Control cable with blue outer sheath, see
    Flexible Control Cables
  • with blue outer sheath for hazardous areas
    to hazard type -i- for intrinsically safe
    installation acc. to DIN EN 60079-14
    section 12.2.2 (VDE 0165 part 1)
  • AWG sizes are approximate equivalent
    values. The actual cross section is in mm².
Application
Instrumentation cables are used in data processing and process control. Instrumentation cables are suitable for fixed installations in damp locations, in open spaces and for underground laying.
CE = Product conforms with Low-Voltage Directive 2014/35/EU.
Downloads
Data sheet
Certificate of compliance

Part no.

No.pairs x
cross-sec.
mm²

Sheath
colour

Outer Ø

approx. mm

Cop.
weight

kg / km

Weight

approx. kg / km

AWG-No.

20099

1 x 2 x 0,5

black

7,5

15,0

74,0

20

20100

2 x 2 x 0,5

black

9,8

30,0

117,0

20

20101

4 x 2 x 0,5

black

11,3

50,0

140,0

20

20233

6 x 2 x 0,5

black

13,1