PAAR-TRONIC-CY

flexible, screened, colour coded to DIN 47100, meter marking, EMC-preferred type

Logo Image
Produktfoto
Technical data
  • Special PVC data cables for
    electronic control adapted to
    DIN VDE 0812 and 0814
  • Temperature range
    flexing -5°C  to  +80°C
    fixed installation -30°C  to  +80°C
  • Operating peak voltage  350 V
    (not for heavy current installation purposes)
  • Test voltage
    core/core  1200 V
    core/screen  800 V
  • Breakdown voltage
    min. 2400 V
  • Insulation resistance
    min. 20 MOhm x km
  • Mutual capacitance  at 800 Hz
    core/core  0.14 mm²  app. 120 pF/m
    core/core  0.25 mm²  app. 150 pF/m
    core/screen  0.14 mm²  app. 240 pF/m
    core/screen  0.25 mm²  app. 270 pF/m
  • Inductance
    approx. 0.65 mH/km
  • Impedance
    approx. 78 Ohm
  • k1-coupling
    approx. 300 pF/100 m
  • Coupling resistance
    max. 250 Ohm/km
  • Minimum bending radius
    flexing 10x cable Ø
    fixed installation 5x cable Ø
  • Radiation resistance
    up to 80x106 cJ/kg (up to 80 Mrad)
Cable structure
  • Bare copper conductor, from 0,5 mm²
    fine wire acc. to DIN VDE 0295 cl.5 /
    BS 6360 cl.5 / IEC 60228 cl.5
  • Conductor construction:
    0,14 mm² = 18x0,1 mm
    0,25 mm² = 14x0,15 mm
    0,34 mm² = 7x0,25 mm
  • Core insulation of special PVC
    compound type TI2 to
    DIN VDE 0207-363-3 / DIN EN 50363-3
  • Core identification (pair) to DIN 47100
  • Cores stranded in pairs with
    optimal lay length
  • Pairs stranded in layers with
    optimal lay length
  • Foil wrapping
  • Drain wire, tinned
  • Tinned copper braided screen,
    approx. 85% coverage
  • Outer sheath of special PVC
    compound type TM2 to
    DIN VDE 0207-363-4-1/DIN EN 50363-4-1
  • Sheath colour: grey (RAL 7032)
  • With meter marking
Properties
  • Extensively oil resistant,
    oil-/chemical resistance
    see "Technical Information"
  • The materials used during manufacturing
    are cadmium-free, contain no silicone
    and are free from substances harmful
    to the wetting properties of lacquers
Tests
  • PVC self-extinguishing and flame retardant
    acc. to DIN VDE 0482-332-1-2 /
    DIN EN 60332-1-2 / IEC 60332-1-2
Note
  • AWG sizes are approximate equivalent
    values. The actual cross section is in mm².
  • Unscreened analogue type:
    PAAR-TRONIC
Application
These data control cables are used for flexible use with free movement without tensile stress or forced movements in dry, moist and wet rooms but not suitable for open air. PAAR-TRONIC-CY is well suited for use in areas subject to signal interference. The high level of screening reduces substantially the effects of electrical disturbances from parallel running wiring etc. The copper screening is also often used as an "earth". The twisted pairs conform favourable cross-talk attenuation values.
EMC = Electromagnetic compatibility
To optimize the EMC features we recommend a large round contact of the copper braiding on both ends.
CE = Product conforms with Low-Voltage Directive 2014/35/EU.
Downloads
Data sheet
Certificate of compliance

Part no.

No.pairs x
cross-sec.
mm²

Outer Ø

approx. mm

Cop.
weight

kg / km

Weight

approx. kg / km

AWG-No.

21001

1 x 2 x 0,14

4,0

15,6

34,0

26

21002

2 x 2 x 0,14

5,0

18,5

40,0

26

21003

3 x 2 x 0,14

5,7

23,0

49,0

26

21004

4 x 2 x 0,14

6,1

26,6

55,0

26

21005

5 x 2 x 0,14

6,8

30,7

66,0

26

21006

6 x 2 x 0,14

7,2

48,5

86,0

26

21007

7 x 2 x 0,14

7,2

51,1

91,0

26

21008

8 x 2 x 0,14

8,2

53,