NSHXAFö 3 kV

halogen-free Special Rubber-Insulated Cable, VDE approved, short-circuit up to 1000 V

Logo Image Logo Image
Produktfoto
Technical data
  • Special rubber core cable acc. to
    E DIN VDE 0250 part 606
  • Temperature range
    flexing -25°C to +70°C
    fixed installation -40°C to +90°C
  • Permissible operating temperature
    at conductor +90°C
  • Nominal voltage U0/U 1,8/3 kV
  • Highest permissible operating voltage
    in three-phase and one-phase
    a.c. systems U0/U 2,1/3,6 kV
    in d.c. systems U0/U 2,7/5,4 kV
  • Test voltage 6 kV
  • Minimum bending radius
    flexing 10x outer Ø
    fixed 6x outer Ø
Cable structure
  • Tinned copper conductor, fine wire
    to DIN VDE 0295 cl.5, BS 6360 cl.5
    and/or IEC 60228 cl.5
  • EPR-insulation, 3GI3 acc. to DIN VDE 0207
    part 20
  • Outer casing: halogen-free polymer
    compound HM3 acc. to
    DIN VDE 0207 part 24
  • Colour black
Properties
Tests
  • Corrosiveness of corrosive gases
    acc. to DIN VDE 0482 part 267,
    DIN EN 50267-2-2, IEC 607542
    (equivalent DIN VDE 0472 part 813)
  • Smoke density
    acc. to DIN VDE 0482
    part 1034-1+2, DIN EN 61034-1+2,
    IEC 61034-1+2, BS 7622 part 1+2
    (equivalent DIN VDE 0472 part 816)
  • Oil resistant
    acc. to DIN VDE 0473-811-404,
    DIN EN 60811-404
  • Behaviour in fire
    to DIN VDE 0482-332-1-2
    DIN EN 60332-2-1, IEC 60332-1 (equivalent
    DIN VDE 0472 part 804 test method B)
Note
  • AWG sizes are approximate equivalent
    values. The actual cross section is in mm².
Application
Particularly suitable for protection against short circuits in laying and for inherently earth-fault-proof routing in rail vehicles and omnibuses. Also suitable for laying in dry environments. In switching units and distributors, they are considered to be short circuit and inherently earth proof to
1000 V. Note: Considered as being short-circuit safe and inherently earth-fault-proof are those operating materials and conducting assemblies where because of suitable measures and/or means applied, neither a short circuit nor a short to ground is to be expected under operating conditions which are in accordance with those specified for the intended application.
Downloads
Data sheet
Certificate of compliance

Part no.

No.cores x
cross-sec.
mm²

Outer Ø

max. mm

Cop.
weight

kg / km

Weight

app. kg / km

AWG-No.

38517

1 x 1,5

7,0

14,4

62,0

16

38518

1 x 2,5

7,5

24,0

76,0

14

38519

1 x 4

9,0

38,0

95,0

12

38520

1 x 6

9,5

58,0

140,0

10

38521

1 x 10

11,0

96,0

190,0

8

38522

1 x 16

13,0

154,0

270,0

6

38523

1 x 25

15,0

240,0

410,0