NAYCWY

power cable, 0,6/1 kV, with concentric copper conductor, VDE approved

Logo Image Logo Image
Produktfoto
Technical data
  • Power and control cable to
    DIN VDE 0276 part 603,
    HD 603 S1 and IEC 60502
  • Temperature range
    flexing -5°C to +50°C
    fixed installation -40°C to +70°C
  • Permissible operating temperature
    at conductor +70°C
  • Permissible short circuit temperature
    (short circuit duration max. 5 s)
    +160°C
  • Nominal voltage U0/U 0,6/1 kV
  • Test voltage 4 kV
  • Max. permissible tensile stress
    with cable grip at conductor
    30 N/mm²
  • Minimum bending radius
    12x cable Ø
Cable structure
  • Aluminium-conductor, to DIN VDE 0295
    cl.1 or cl.2, single-wire or multi-wire,
    BS 6360 cl.1 or cl.2, IEC 60228
    cl.1 or cl.2
  • Core insulation of PVC
    compound type DIV4 to HD 603 S1
  • Core identification DIN VDE 0293-308
  • Cores stranded concentrically
  • Filling compound
  • Concentric conductor (Ceander),
    inner layer of corrugated copper wires,
    outer layerwith copper tape
  • Outer sheath of PVC
    compound type DMV5 to HD 603 S1
  • Sheath colour: black
Properties
  • The materials used during manufacturing
    are cadmium-free, contain no silicone
    and are free from substances harmful
    to the wetting properties of lacquers
  • Tests
    • PVC self-extinguishing and flame retardant
      acc. to DIN VDE 0482-332-1-2,
      DIN EN 60332-1-2, IEC 60332-1 (equivalent
      DIN VDE 0472 part 804 test method B)
    Highest permissible voltage
    • Direct current systems 1,8 kV
    • Alternating current systems
      • Single-phase systems
      both outer conductors insulated 1,4 kV
      • Single-phase systems
      one outer conductor earthed 0,7 kV
    • Three-phase systems 1,2 kV
      with concentric conductor and
      a cross section from 240 mm² 3,6 kV
Note
  • re = round conductor, single-wire
    rm = round conductor, multi-wire
    sm = sectional conductor, multi-wire
  • AWG sizes are approximate equivalent
    values. The actual cross section is in mm².
Application
Power distribution cables, preferably used for underground installation, primarily in local networks, for industrial applications and switching systems, power stations. Wherever increased electrical and mechanical protection are required. Installation in water, outdoors, in concrete, indoors and in cable ducts. The concentric conductor (C) can be used as a PE or PEN conductor or as a screen. The corrugated design (Ceander) of the conc entric conductor permits any number of cable junctions during assembly, without any conductors having to be cut. This ensures a optimal reliability.
CE = Product conforms with Low-Voltage Directive 2014/35/EU.
Downloads
Data sheet
/opc/workarea/suppliers/STD/documents/pdf/wb/1WB_36009_en.pdf

Part no.

No.cores x
cross-sec.
mm²

Outer Ø

app. mm

Cop.
weight

kg / km

Alu weight

kg / km

Weight

app. kg / km

AWG-No.

36009

3 x 10

re / 10

20,2

88,0

87,0

603,0

8

36010

3 x 16

re / 16

22,3

125,0

139,0

754,0

6

36011

3 x 25

re / 25

25,5

170,0

218,0

1043,0

4

36012

3 x 25

rm / 16

26,6

125,0