OZ-BL

outer sheath blue, intrinsic safety, flexible, meter marking

Logo Image Logo Image
Produktfoto
Technical data
  • Control cable, special PVC with blue outer
    sheath for hazardous areas to
    hazard type -i- (= intrinsically safe)
  • For intrinsically safe installation acc. to
    DIN EN 60079-14 and IEC 60079-14
    section 12.2.2 (VDE 0165 part 1)
  • Temperature range
    flexing -15°C to +80°C
    fixed installation -40°C to +80°C
  • Nominal voltage
    U0/U 300/500 V
  • Test voltage
    3000 V
  • Breakdown voltage
    min. 6000 V
  • Mutual capacitance
    core/core  approx. 120 nF/km
  • Inductance
    approx. 0,68 mH/km
  • Minimum bending radius
    flexing 7,5x cable Ø
    fixed installation 4x cable Ø
  • Radiation resistance
    up to 80x106 cJ/kg (up to 80 Mrad)
Cable structure
  • Bare copper conductor, to
    DIN VDE 0295 cl.5, fine wire,
    BS 6360 cl.5, IEC 60228 cl.5
  • Core insulation of special PVC
    compound type Z 7225
  • Core identification to DIN VDE 0293
    black cores with continuous white
    numbering
  • without GN-YE conductor
  • Cores stranded in layers with
    optimal lay length
  • Outer sheath of special PVC
    compound type TM2 to
    DIN VDE 0207-363-4-1/DIN EN 50363-4-1
  • Sheath colour: blue (RAL 5015)
  • With meter marking
Properties
  • Extensively oil resistant,
    oil-/chemical resistance
    see table Technical Informations
  • The materials used during manufacturing
    are cadmium-free, contain no silicone
    and are free from substances harmful
    to the wetting properties of lacquers
Tests
  • PVC self-extinguishing and flame retardant
    acc. to DIN VDE 0482-332-1-2,
    DIN EN 60332-1-2/IEC 60332-1 (equivalent
    DIN VDE 0472 part 804 test method B)
Note
  • For underground laying use NYY with blue
    outer sheath.
  • AWG sizes are approximate equivalent
    values. The actual cross section is in mm².
  • Instrumentation cable RE-2Y(St)Yv with blue
    outer sheath see Data and Computer Cables
Application
For hazardous areas the cables with special marking (blue) (hazard type-i-) used as flexible control and measuring cables to meet the requirements for the installation of electrical apparatus. These installations are not earthed and require a separate power circuit. Those cables are not suitable for underground laying.
CE = Product conforms with Low-Voltage Directive 2014/35/EU.
Downloads
Data sheet
Certificate of compliance

Part no.

No.cores x
cross-sec.
mm²

Outer Ø

approx. mm

Cop.
weight

kg / km

Weight

approx. kg / km

AWG-No.

14001

2 x 0,75

5,3

14,4

46,0

19

14002

3 x 0,75

5,6

21,6

54,0

19

14003

4 x 0,75

6,3

29,0

66,0

19

14004

5 x 0,75

6,9

36,0

80,0

19

14075

7 x 0,75

7,5

52,0

110,0

19

14005

8 x 0,75

8,3

58,0

130,0

19

14076

12 x 0,75

9,8

88,0

179,0

19

14006

18 x 0,75

12,2

130,0

257,0

19

14007

25 x 0,75

14,3

180,0

365,0

19

14008

30 x 0,75

15,3

215,0

448,0

19

14009

34 x 0,75

16,5

245,0

510,0

19

14010

41 x 0,75

18,1

298,0

607,0

19

14011

2 x 1

5,6

19,0

60,0

18

14012

3 x 1

5,9

29,0

72,0

18

14013

4 x 1

6,6

38,0

86,0

18

14014

5 x 1

7,3

48,0

104,0

18

14015

7 x 1

8,1

67,0

141,0

18

14016

12 x 1

10,4

115,0

230,0

18

14017

18 x 1

12,9

173,0

343,0

18

14018

25 x 1

15,4

240,0

485,0

18

14019

2 x 1,5

6,4

29,0

70,0

16

14020

3 x 1,5

6,8

43,0

90,0

16

14021

4 x 1,5

7,4

58,0

109,0

16

14022

5 x 1,5

8,3

72,0

131,0

16

14023

7 x 1,5

9,2

101,0

184,0

16

14024

12 x 1,5

11,8

173,0

309,0

16

14025

18 x 1,5

14,6

259,0

440,0

16

14026

25 x 1,5

17,4

360,0

620,0

16

14027

30 x 1,5

18,6

440,0

842,0

16

14100

3 x 2,5

8,3

72,0

148,0

14

14101

4 x 2,5

9,2

96,0

178,0

14

14102

5 x 2,5

10,1

120,0

221,0

14