TRAYCONTROL 600 and 600-C now certified for Oil Res II usage

Our bestsellers, the TRAYCONTROL 600 and 600-C control cables, have passed the Underwriter's Laboratory (UL) Oil Resistance II test. The cables now have both Oil Res I and II ratings, making them ideally suited for applications where cables are exposed to oil and excessive temperatures for long durations.

Oil combined with other degradation mechanisms, such as temperature, can cause significant damage to cables over time and shorten their useful life. To pass the UL's Oil Resistance II test, samples of the TRAYCONTROL 600 and TRAYCONTROL 600-C had to maintain 65% of their tensile and elongation properties after being immersed in oil for 60 consecutive days at temperature of 167°F (75°C). The cables also underwent observation in order to determine if any physical damage, caused by oil exposure at elevated temperatures, had occurred. After testing the specially formulated PVC jacket passed the necessary requirements when compared to pre-tested samples.